EECS Instructional Support, University of California at Berkeley
[ ISG home page ] [ who we are ] [ send us email ] [ search ] [ FAQ ]

EECS labs in Hearst Memorial Mining Building (HMMB)
planned occupancy: Fall 2002

Proposed Plans for the Labs:


260/262 HMMB   [Acroread] [Postscript]


360 HMMB   [Acroread] [Postscript]


362 HMMB   [Acroread] [Postscript]


364 HMMB   [Acroread] [Postscript]


Specifications

  • Labs: computers, networks, power, telephone:

    Room computers 100mb ports VLAN server 110V AC outlets printers phone jacks square feet
    262 HMMB 19 SunRays 36 E450 server A 72 3 4 779
    360 HMMB 36 SunRays 44 E450 server B 88 0 4 1558
    362 HMMB 24 SunRays 28 E450 server B 56 2 2 736
    364 HMMB 36 SunRays 44 E450 server A 88 0 4 1558
    Totals 115 SunRays 152 ports --- 308 outlets 5 printers 14 phone jacks 4631 sq ft

    Network:
         +-----------------------+  (1)                          
         | server A in 253 HMMB: +======== SWITCH A (263 HMMB) ======== to INTERNET
         | SunRay server         |         (CNS) 
         |                       |  (1)                          (36) 
         | 3 ethernet cards      +======== SWITCH B (263 HMMB) ======== to 262 HMMB
         |                       |         (EECS)
         | 128.32.___.___        |  (1)                          (44)
         | ___.eecs.berkeley.edu +======== SWITCH C (263 HMMB) ======== to 360 HMMB
         +-----------------------+         (EECS)
    	
         +-----------------------+  (1)                          
         | server B in 253 HMMB: +======== SWITCH A (263 HMMB) ======== to INTERNET
         | SunRay server         |         (CNS)
         |                       |  (1)                          (28) 
         | 3 ethernet cards      +======== SWITCH D (263 HMMB) ======== to 362 HMMB
         |                       |         (EECS)
         | 128.32.___.___        |  (1)                          (44)
         | ___.eecs.berkeley.edu +======== SWITCH E (263 HMMB) ======== to 364 HMMB
         +-----------------------+         (EECS)
    	
         +-----------------------+  (1)                          
         | server C in 253 HMMB: +======== SWITCH A (263 HMMB) ======== to INTERNET
         | Firewall + printers   |         (CNS)
         |                       |  (1)                          
         | 2 ethernet cards      +======== SWITCH F (263 HMMB) +======= to 262 HMMB
         |                       |         (EECS)              +======= to 360 HMMB
         | 128.32.___.___        |                             +======= to 362 HMMB
         | ___.eecs.berkeley.edu +                             +======= to 364 HMMB
         +-----------------------+
    
    
                                    8 spare 100mb cables to 263 HMMB
        

  • Machine Rooms: computers, networks, power, telephone:

    Room computers 100mb ports approx Power 110V AC outlets printers phone jacks
    253 HMMB 3 servers, 2 UPSs   * 16   ** 4000 VA 16 0 2
    263 HMMB 5 switches   *** 176   ** 300 VA 12 (CNS) (CNS)
    Totals            

    EECS Server Room (253 Hearst):   (maintained by EECS Inst)
  • 8' x 8'
  • (2) Sun Enterprise servers (4GB+ RAM, 4+ SPARC cpus); tape stacker  * 
      max power consumption per server: 110V, 15A, 1664W
      max heat output per server: 5680 BTU/hr
      size per server: 23" high, 18" wide, 28" deep
      weight per server: 205 lb
      running Solaris and SunRay Enterprise Server software
  • (1) firewall system for internet-enabled printer, laptop & WEBcam ports  * 
      max power consumption per server: 110V, 10A, 330W
      max heat output per server: 1122 BTU/hr
      size per server: 18" high, 12" wide, 18" deep
      weight per server: 50 lb
      running SolarisX86 or Linux
  • (2) 3000 VA UPS  * 
      max power consumption per UPS: 110V, 30A, 2250W
      max heat output per UPS: 7650 BTU/hr
      These are UPSs; this load is for full charging and is very unlikely.
  • related jumper blocks, jumpers and cabling
  • related rack hardware
  • Ventilation: exhaust vent and temperature-controlled fan. (1-ton A/C unit was discussed, not needed)
  • Note: wattage * 3.4 = BTUs
  • TeleCom closet (263 Hearst):   (maintained by IS&T CNS)

  • 16' x 9'
  • (16) 100mb cables to 253 Hearst  ** 
  • (152) 100mb cables to 262/360/362/364 Hearst  ** 
  • (1) 100mb or 1-GB uplink to internet ring
  • (1) 24-port 10/100 Mb switch  *** 
      This switch will connect to the Internet.
      This switch will be maintained by IS&T CNS.
      For Internet-connected systems (servers, printers and laptops) in EECS machine room (253 HMMB) and 4 labs (262, 360, 362, 364 HMMB).
  • (4) 48-port 10/100 Mb switches  *** 
      For internal private nets.
      One per lab (262, 360, 362, 364 HMMB) for SunRays behind "firewall"
  • related jumper blocks, jumpers and cabling
  • related rack hardware
  • Furniture:

    Room 72"x30" tables  +  36"x30" ADA tables  +  4-person conference tables 8-person conference tables chairs
    253 HMMB 2 0 0 0 5
    262 HMMB 9 1 2 1 35
    360 HMMB 17 2 0 0 36
    362 HMMB 11 2 0 0 24
    364 HMMB 17 2 0 0 36
    Totals 56 tables 7 tables 2 tables 1 tables 136 chairs
       +  removable, 16" high, 9" deep shelves over monitors
     +  cable control raceways attached to back of table

  • Media:

    Room 6' whiteboards 12' whiteboards 6' bulletin boards 6' projection screens
    253 HMMB 1 0 1 0
    262 HMMB 6 1 0 1
    360 HMMB 2 0 0 1
    362 HMMB 0 0 2 0
    364 HMMB 2 0 0 1
    Totals 11 1 3 3

    Other equipment:
  • (2) LCD ceiling-mounted projectors   (360 & 364 Hearst)
  • (2) WEB cams   (portable)
  •  
      Kevin Mullally, Manager
      EECS Instructional Support Group
      
      Friday, January 17, 2003


    email: